PROMAT make 2 Hours fire rated doors system duly tested for integrity & Insulation as per the IS:3614 part 2 and BS:476 part 22 at FRL CBRI.
Roorkee with standard heating conditions as specified in IS:3809 - 1979 and BS:476 part 20 & 22 1987 to achieve the required integrity & insulation.
Providing, Supply & Fixing of RADIANT make 2 Hours fire rated door system duly tested as per the IS:3614 part 2 and BS:476 part 20 at FRL CBRI
Roorkee with standard heating conditions as specified in IS:3809 - 1979 and BS:476 part 20 & 22 1987 to achieve the required Fire Rating.
Automatic Fire Curtain
They provide 240 minutes of continuous fire containment with a standard drop down system.
Each curtain is suspended on a single barrel up to 6 metres wide and 8 metres high.
Overlapping curtains are used to protect larger areas, please see our architect’s page for more information on our multi-barrelled fire curtain systems.
Firesafe 240 Automatic Fire Curtains are slightly heavier and thicker than the Firesafe 60 curtains but are still much lighter and easier to install than roller shutters.
Protect areas up to 30 metres wide.
Unobtrusive, lightweight and easy to install.
Alternative to a fire door, fire shutter or sprinkler system.
Option to be fully recessed into the walls and ceiling.
Excellent for atriums, lift shafts protected lobbies and stairwells, offices and high-rise buildings.
Fire Motors & Cable Coating
Fire Barriers using Fire Stop Mortar Seal shall be installed at following locations. The thickness of Fire Barrier shall be sufficient to achieve 3 hrs. fire rating.
Panel bases in control room shall be sealed (wherever any other type of fire sealing system is not already installed and wherever it is structurally and maintenance wise
feasible to install).
All wall openings and floor openings in control room / cable vaults shall be sealed.
.All cable entry openings from trenches or overhead cable trays racks shall be sealed.All vertical cables coming out below the panels shall be coated to a full length of vertical drop from bottom of panel plus 1.5 to 2.5 mtrs. Horizontal run after the bend.
All vertical cable runs anywhere in the area are to be coated full.All horizontal cable runs to be coated for a length of 1.5 mtrs at an interval of every 2 to 3 mtrs.
Barriers shall be installed inside the trenches at every intersection or Tee joints and bends at every 2 meters from centre line of cable rack inside the trench.
Alternative to a fire door, fire shutter or sprinkler system.
Barriers shall be installed at every 15 meters in straight runs oftrenches.
>All vertical cables coming down into the trenches from the equipment are to be coated full.
Woodkot
RECOMMENDED USE : Applied on doors, windows,wall paneling, false ceilings, fiber board tiles to render them fire resistant to class 1 surface spread of flame as per BS-476 part 7.
PHYSICAL DATA
COLOUR: White/off white (any shade can be matched
by adding desired stainer) FINISH Glossy/Semi glossy
Touch dry: 2Hours Hard dry: 8 Hours Full cure: 7 Days (At 30 degree C and 65% Relative humidity)
APPLICATION: By Brush / By spray
RECOMMENDED DFT: 60microns per coat
OVERCOATING INTERVAL MIN: 8 hours; MAX: 24 hours If exceeds, the surface should be roughened by emery scuffing.
Fabkot
National Building Code Part IV, para 11.6.1 states: "For
assembly buildings, all fabrics and stage settings
made of combustible materials should be treated with
flame of proofing materials"
After the application of Fabkot on fabric it becomes Flame Proofed Fabric.
This flame proofed fabric when in contact with fire, will only char but will not spread flame thereby stopping propagation of fire completely.
In the case of Non-
Durable treatment the flame proofing treatment has to
be repeated after every water wash.
Usage: Makes cotton & non-synthetic fabrics like curtains, furnishing cloth, carpets including jute/choir carpets, grey canvas, cardboard, paper & similar material flame proof
Usage: Makes cotton & non-synthetic fabrics like curtains, furnishing cloth, carpets including jute/choir carpets, grey canvas, cardboard, paper & similar material flame proof
Application: Dip or spray the material that has to be treated, must be soaked and squeezed in such a manner that after drying, the weight of the material increases by about 15 to 18%. Ordinarily this can be achieved by dipping or spraying on the material till fully wet as required for the duration of 2 to 10 minutes. Grey canvas should be soaked for 1 hour to 24 hours depending upon its weight.